Description
Product Details
This is a 16A, 25kA, 1 module, single pole, outgoing MCCB. It has a NZM1 frame and is to be used with Memshield 3 items. It has a maximum cable capacity of 70mm². Dimensions: 145x30x73mm.This is a Molded Case Circuit Breaker (MCCB) that provides overload and short-circuit protection for electrical circuits. It is a single-pole breaker, meaning that it protects one circuit at a time. This has a 16A rating, which means that it can safely carry a current of up to 16A. It also has a 25kA short-circuit rating, which means that it can safely interrupt a short-circuit current of up to 25kA.This is a member of Eaton’s Memshield 3 family of MCCBs. Memshield 3 is a patented technology that provides enhanced protection against arc flash hazards. Arc flash is a sudden release of electrical energy that can cause severe burns and other injuries. Memshield 3 helps to reduce the risk of arc flash by providing a barrier between the live parts of the circuit breaker and the operator.This is a safe and reliable way to protect electrical circuits. It is a valuable tool for any electrician or facility manager.
- Release system Thermomagnetic release
- Number of poles 1 pole
- Installation type Fixed
- Standard/Approval IEC
Technical Specifications
Moulded case circuit breaker (MCCB) |
|
Overload release current setting | 16 – 16 A |
---|---|
Complete device with protection unit | Yes |
DIN rail (top hat rail) mounting optional | No |
Motor drive optional | No |
Integrated earth fault protection | No |
Suitable for DIN rail (top hat rail) mounting | No |
Motor drive integrated | No |
Switched-off indicator available | No |
With integrated under voltage release | No |
Adjustment range undelayed short-circuit release | 320 – 320 A |
Rated voltage | 230 – 230 V |
Adjustment range short-term delayed short-circuit release | 0 – 0 A |
Position of connection for main current circuit | Front |
---|---|
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz | 25 kA |
Number of auxiliary contacts as change-over contact | 0 |
Number of poles | 1 |
Number of auxiliary contacts as normally closed contact | 0 |
Rated permanent current Iu | 16 A |
Number of auxiliary contacts as normally open contact | 0 |
Device construction | Built-in device fixed built-in technique |
Type of electrical connection of main circuit | Frame clamp |
Type of control element | Rocker lever |
Degree of protection (IP rating) | IP20 |
Reviews